Back to Product
Ref: XH-SUB-2026-0491
XINHUAN Submittal Package
Anhui XinHuan Electrical Power Equipment Co., Ltd. | Hefei Manufacturing Base
CNAS Test Certified | ISO 9001:2015 | ISO 14001:2015 Registered OEM
SUBMITTAL REF: XH-SUB-2026-0491
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Isolation Transformers

ZSG Three-Phase Dry-Type Rectifier Transformer

Submittal Specification Datasheet & Engineering Technical Parameters

1. Electrical Technical Parameters & Ratings

Parameter Specification Design Rating & Certified Value
Rectifier Configuration 6-Pulse or 12-Pulse bridge rectifier compatible
AC Grid Input 380V, 415V, 440V, 480V, 660V
DC Output Matching Custom secondary voltage and high current ratings
Harmonic Capability Reinforced copper busbars and eddy current suppression

Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)

IEEE C57.12.00 / IEC 60076-1
Electromagnetic Parameter Design Characteristic & Certified Benchmark Grid Study Application
Saturation Knee-Point Voltage (\(V_k\)) 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) Overvoltage & Ferroresonance Protection
Air-Core Reactance (\(X_{\text{air}}\)) \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) Deep Saturation Inrush Peak Limit
Air-Core Inductance (\(L_{\text{air}}\)) \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) PSCAD Saturable Core / UMEC Modeling
Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) Protective Relay Coordination & POI Voltage Dip
Magnetizing Inrush Decay Constant (\(\tau\)) \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) Differential Relay (87T) Harmonic Restraint
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection? Interactive V-I Calculator

2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile

2D AutoCAD Blueprint
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic

Dimensional & Installation Requirements

  • Foundational Base: Steel channel Skid / Sub-station Pad Mounting.
  • Bushings Orientation: HV top-mounted / side-cabinet entry option.
  • Grounding Terminals: Dual M12 copper grounding pads on diagonal corners.
  • Enclosure Protection: IP54 Outdoor Corrosive C4/C5 Marine Paint Coating.
  • CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.

3. Factory Acceptance Testing (FAT) & Routine Test Protocol

Every transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with IEC 60076-1 before dispatch. Routine test certificates are included in the shipment package.

1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)

4. Seaport Logistics, Packaging & Warranty Terms

Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]
Submittal Document Code: XH-SUB-2026-0491 — Confidential Technical Datasheet