Dry-Type Transformers Cast Resin (SCB Series) SKU: 1600_KVA_10KV_SCB13_THREE_PHASE_CAST_RESIN_DRY_TYPE_TRANSFORMER

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer

This 1600 kva scb13 three-phase cast resin dry-type transformer is designed for indoor power distribution where safety, low maintenance, and practical insulation performance are important. It provides dependable service for commercial, industrial, infrastructure, or special-application installations and can be customized according to voltage, enclosure, cooling, and monitoring requirements.

Compliance Standards
IEC • ANSI • IEEE • GB
Quality Inspection
100% FAT Routine Tested
Engineering CAD
2D CAD / SLD Schematics
Global Logistics
Direct Seaport CIF Export
Engineering Datasheet

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — Technical Parameters & Ratings

Print Submittal Datasheet IEC / ANSI Certified Factory Standard
Model Series SCB10 / SCB11 / SCB13 / SCB14
Rated Capacity 1600 kVA
Primary Voltage (U1) 10,000 V (10 kV / 11 kV)
Secondary Voltage (U2) 400 V / 415 V / 480 V (3-Phase 4-Wire)
Vector Group Dyn11
Rated Frequency 50 Hz / 60 Hz
Cooling Method AN (Natural Air) / AF (Forced Air Blower)
Primary Current (I1) 92.38 A
Secondary Current (I2) 2086.8 A
Guaranteed No-Load Loss (P0) 2690 W
Guaranteed Load Loss (Pk at 120°C) 11730 W
Short-Circuit Impedance (Uk) 4.5%
Insulation Class F Class (155°C) / H Class (180°C) Epoxy Cast Resin
Temperature Rise Limit Winding Temp Rise ≤ 100 K (F Class) / ≤ 125 K (H Class)
IP Protection Class IP00 (Open Type) / IP20 (Indoor Enclosure) / IP23 (Loubered)
Total Weight 5300 kg
Overall Footprint (L×W×H) 1750 mm × 1200 mm × 1780 mm
Governing Standards IEC 60076-11, GB/T 10228-2015, CE, ISO 9001

Technical Highlights

  • This product offers the advantages of indoor safety, low maintenance, and practical installation flexibility. It supports projects that need reliable electrical performance, oil-free operation, and configurable insulation, enclosure, monitoring, or cooling features for modern indoor distribution systems.

Application Scenarios

  • Commercial buildings and office complexes
  • Hospitals, schools, and public facilities
  • Industrial workshops and manufacturing plants
  • Data centers and mission-critical electrical rooms
  • Indoor infrastructure and utility support projects

Key Features

  • 1600 kVA rated capacity for safe indoor distribution and equipment supply
  • Dry-type insulation system suitable for indoor, low-maintenance installations
  • Three-phase construction for commercial, industrial, infrastructure, or special applications
  • Available with customized voltage ratio, enclosure, monitoring, and cooling options
  • Supports project-based IEC specifications and export-oriented documentation
  • Designed for dependable service where oil-free installation is preferred

Optional Configurations

  • High-voltage and low-voltage rating
  • Enclosure level: IP00 / IP20 / IP23 / customized
  • Temperature controller and smart monitoring options
  • Cooling mode: AN / AF and fan arrangement
  • Winding material and insulation class
  • Project-specific standards and test document requirements
  • Color, nameplate language, and document package
  • Ambient temperature, altitude, and installation condition adaptation

Engineering Submittal & Layout Workbench

Substation Room Fit & Multi-Equipment CAD Footprints

Select your equipment type and capacity to inspect verified GA engineering CAD line drawings, Single Line Diagrams (SLD), dimensions (L × W × H), roller gauge, and submittal clearances before procurement.

Available Ratings:
IEC 60076-1 Submittal Specs
XinHuan Engineering GA CAD Drawing
XinHuan Engineering Single Line Diagram (SLD)
11kV / 33kV Dual Voltage
IEC 60076 / IEEE Compliant
100% Routine Factory Tested
Export Nitrogen / Seaworthy Pack

1000 kVA Technical Dimensions

IEC 60076-1

International utility & industrial submittal specifications

Overall Length (L) 1,750 mm
Overall Width (W) 1,120 mm
Overall Height (H) 1,780 mm
Roller Wheel Track Gauge (D) 820 mm
Total Equipment Net Weight 3,820 kg
Min Substation Clearance 1,000 mm surrounding
Rated Voltage / System 11 kV / 33 kV Dual Primary
Applicable Standard IEC 60076-1 / IEEE C57
Download Technical Data Sheet (PDF) Request Factory Engineering Submittal Package

Full CAD DXF/DWG vector footprints, 3D STEP models, and custom project submittals provided within 2 hours upon request.

PSCAD™ & ETAP® Grid Simulation

Non-Linear V-I Saturation Curve & Air-Core Inductance (\(L_{\text{air}}\))

Precision core excitation characteristics, non-linear knee inflection (\(V_k\)), and air-core reactance (\(X_{\text{air}}\)) calibrated for 1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer.

Full Engineering Suite
Quick Rating Switch
kVA
kV
%
2.10
1.80 (Compact Shell) 2.10 (Standard IEEE / CIGRE) 2.50 (Outer HV Layer)
Air-Core Inductance (\(L_{\text{air}}\)) 18.7× In Peak
81.65 mH
Reactance
25.65 Ω
Knee \(V_k\)
13.0 kV
Decay \(\tau\)
0.17 s
Request Certified Factory Excitation & Inrush Submittal
Non-Linear Magnetization Characteristic (\(\lambda - I_{\text{exc}}\)) Interactive Vector Plot
Linear Core Zone Knee Transition Air-Core Slope (\(X_{\text{air}}\))
PSCAD Simulation Point Voltage (\(V_{\text{pu}}\)) Flux (\(\lambda\), Wb-t) Current (\(I_{\text{pu}}\)) Current (A)
Data formatted for direct entry into PSCAD Classical Saturable Transformer and UMEC core components per IEEE C57.12.00 & CIGRE 33.02.
1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — XinHuan Cast Resin Dry-Type Transformer Winding Workshop
XinHuan Hefei Manufacturing Plant — Precision Winding & Assembly Line
Factory Build Quality

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — Internal Construction & Premium Materials

Built with tier-1 certified raw materials engineered for long operational life (>30 years), superior dielectric withstand, and high short-circuit withstand capacity.

Silicon Steel Core

High-grade grain-oriented cold-rolled silicon steel with step-lap mitered joints for low $P_o$ losses.

100% Copper Windings

Electrolytic oxygen-free copper with high thermal grade insulation for surge resistance.

Precision Tap Changer

De-energized tap switch ($\pm 2 \times 2.5\%$) or on-load vacuum tap changer (OLTC) optional.

Protection & Sensors

Buchholz gas relay, magnetic oil gauge (MOG), and dial thermometers with alarm contacts.

Quality Assurance

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — 100% Factory Acceptance Testing (FAT)

CNAS & ISO 9001 Certified

Every transformer unit manufactured by XinHuan undergoes mandatory routine factory testing prior to container dispatch. Full certified routine and type test submittal reports are provided with commercial documentation:

1. Insulation Resistance

Megger test (HV to LV, HV to Earth, LV to Earth) >1000 MΩ.

2. Voltage Ratio & Vector

Turns ratio check across all taps with phase displacement check.

3. Winding DC Resistance

Precision Kelvin bridge measurement across all tap positions.

4. Short-Circuit Impedance

Load loss ($P_k$) measurement corrected to reference temp (75°C).

5. No-Load Loss & Current

Core excitation test ($P_o$ and $I_o$) at rated sinusoidal voltage.

6. AC Voltage Withstand

Power-frequency separate source test (e.g. 50kV/70kV 1 min).

7. Lightning Impulse (BIL)

Full wave & chopped wave impulse withstand (BIL up to 170kV).

8. Partial Discharge & Seals

Ultra-low discharge (<5 pC) and pressurized oil/gas tightness test.

Logistics Intelligence

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — Export Packaging & Seaport Logistics

Global CIF / FOB Delivery

The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Technical documents, test reports, nameplate confirmation, and pre-shipment support can be supplied according to order requirements. OEM/ODM support and project-based coordination are available for qualified inquiries.

Production Lead Time

Standard manufacturing cycle is 4 to 6 weeks from approval of GA blueprints and single-line diagrams.

Heavy-Duty Export Packaging

Vacuum moisture barrier preservation, nitrogen blanketing, and reinforced steel-frame structural crate skids.

Direct Seaport Routes

Fast ocean freight to Port of Chancay & Callao (25-35 days), Manila, Lagos, and Middle East ports.

Equipment Video Inspection

100% Tested

Watch XinHuan technicians perform routine dielectric testing, winding insulation checks, and quality inspections inside our Hefei manufacturing plant.

Every unit 100% routine tested before container loading.
Direct Factory Consultation

Need Custom Project Engineering?

Send your single-line diagram (SLD), voltage ratings, or tender specifications. Our chief electrical engineers will review and issue an actionable CIF quotation within 24 hours.

Custom Voltage Ratios
High-Altitude Derating
Short-Circuit Impedance
Third-Party FAT Witness

1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer — Engineering & Procurement FAQs

Frequently asked questions regarding specifications, certifications, and delivery for 1600 kVA 10kV SCB13 Three-Phase Cast Resin Dry-Type Transformer.

Please send us your required capacity, high voltage, low voltage, frequency, cooling preference, and installation conditions for the 1600 kva scb13 three-phase cast resin dry-type transformer. Our team can recommend a suitable configuration and provide a quotation based on your project requirements.

The product can be produced according to IEC standards and customer technical specifications. Routine factory tests, inspection records, and technical documentation can be provided before shipment. Optional configurations for project-specific grid, environmental, and accessory requirements are available upon request.

Standard manufacturing lead time is 4 to 6 weeks following approval of GA blueprints and single-line diagrams. Direct sea container shipping is available under FOB, CFR, or CIF terms with full customs documentation (Bill of Lading, Certificate of Origin, Test Reports).
PARENT ENGINEERING PILLAR IEC 60076-11 · E2/C2/F1 Certified & <5 pC Partial Discharge

11kV Cast Resin Dry-Type Transformers (SCB14/SCB18) Pillar Guide

Compare full capacity no-load loss ($P_0$), load loss ($P_k$), impedance ($U_k\%$), dimensional weights, and routine test tolerances across all models in this series.