SUBMITTAL REF: XH-SUB-2026-0061
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Oil-Immersed Transformers

160 kVA 11kV S22 Amorphous Alloy Three-Phase Oil Transformer

Submittal Specification Datasheet & Engineering Technical Parameters

1. Electrical Technical Parameters & Ratings

Parameter Specification Design Rating & Certified Value
Rated Capacity 160 kVA
Primary Voltage (U1) 11,000 V (11 kV)
Secondary Voltage (U2) 415 V / 240 V (3-Phase 4-Wire)
Vector Group Dyn11
Rated Frequency 50 Hz
Cooling Method ONAN (Oil Natural Air Natural)
Primary Current (I1) 2.8 A
Secondary Current (I2) 222.6 A
Guaranteed No-Load Loss (P0) 290 W
Guaranteed Load Loss (Pk at 75°C) 1980 W
Short-Circuit Impedance (Uk) 4.0%
HV Insulation Level LI 75 / AC 35 (11kV Class)
Temperature Rise Limits Top Oil ≤ 50K, Winding ≤ 55K (45°C Ambient)
Creepage Distance ≥ 31 mm/kV (Outdoor Tropicalized Porcelain)
Core & Coil Weight 430 kg
Insulating Oil Weight 280 kg
Total Assembled Weight 840 kg
Overall Footprint (L×W×H) 1120 mm × 780 mm × 1300 mm
Governing Standards IEC 60076, BS 171, SON NIS, NERC Code

Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)

IEEE C57.12.00 / IEC 60076-1
Electromagnetic Parameter Design Characteristic & Certified Benchmark Grid Study Application
Saturation Knee-Point Voltage (\(V_k\)) 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) Overvoltage & Ferroresonance Protection
Air-Core Reactance (\(X_{\text{air}}\)) \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) Deep Saturation Inrush Peak Limit
Air-Core Inductance (\(L_{\text{air}}\)) \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) PSCAD Saturable Core / UMEC Modeling
Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) Protective Relay Coordination & POI Voltage Dip
Magnetizing Inrush Decay Constant (\(\tau\)) \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) Differential Relay (87T) Harmonic Restraint
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection? Interactive V-I Calculator

2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile

2D AutoCAD Blueprint
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic

Dimensional & Installation Requirements

  • Foundational Base: Steel channel Skid / Sub-station Pad Mounting.
  • Bushings Orientation: HV top-mounted / side-cabinet entry option.
  • Grounding Terminals: Dual M12 copper grounding pads on diagonal corners.
  • Enclosure Protection: IP54 Outdoor Corrosive C4/C5 Marine Paint Coating.
  • CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.

3. Factory Acceptance Testing (FAT) & Routine Test Protocol

Every transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with IEC 60076-1 before dispatch. Routine test certificates are included in the shipment package.

1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)

4. Seaport Logistics, Packaging & Warranty Terms

Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]